Determination of Natural Frequencies of Arch Dams Based on Reservoir Levels Using Ambient and Forced Vibration Tests- Juniper Publishers
Juniper Publishers- Journal of Civil Engineering
Abstract
In this study, the dynamic characteristics such as
natural frequencies of arch dams are investigated using Ambient and
Forced Vibration Tests. For this purpose, a prototype model of Type-1
arch dam considering reservoir and foundation is constructed in the
laboratory conditions. The dam has a single curvature, constant radius
and constant central angle. Also, it has 6 unit height and 0.6 unit
constant widths. To construct a prototype model, 1 unit is selected as
10cm. Therefore, dam height and crest width are designed as 60cm and
6cm, respectively. To identify dynamic characteristics of the arch dam,
ambient and forced vibration tests are conducted for different reservoir
levels; and the variation of natural frequencies is determined using
both Ambient and Forced Vibration Tests. During the ambient vibration
tests the dam vibrated under natural excitations in operation
conditions. During the forced vibration tests, the dam excited by an
impact hammer. From the study, the dynamic characteristics obtained for
different reservoir level are compared with each other. It is seen that
there is a good agreement between both results and they are nearly
closed to each other. Also, the higher reservoir levels significantly
change the behavior of the dam.
Keywords:
Ambient vibration test; Dynamic characteristics; Forced vibration test;
Natural Frequency; Prototype arch dam model; Reservoir level
Abbreviations:
FRF: Frequency Response Function; IRF: Impulse Response Function; PP:
Peak Picking; SSI: Stochastic Subspace Identification; FDD: Frequency
Domain Decomposition techniques; EFDD: Enhanced Frequency Domain
Decomposition; SVD: Singular Value Decomposition; FFT: Fast Fourier
Transform
Introduction
Arch dams generally curved in plan and possibly in
elevation, and they transmits a huge portion of the water pressure and
other loads such as earthquake, wind, ice etc. [1].
They are required advanced engineering knowledge to design, construct
and manage. Although arch dams have multiple benefits, they present a
risk to public safety due to the possibility of a dam failure and the
damage it would cause [2].
Especially, the damage of these dams retaining large quantities of
reservoir include serious risks for life and property during
earthquakes. To prevent these risks, dynamic behavior of the structure
have to be assessed. Ambient vibration Testing (AVT) and Forced
Vibration testing (FVT) are the useful tools to determine the dynamic
properties of structures. The importance of the subject is highligted in
some studies [3-7]. In vibration testing dynamic behavior of a structure is estimated through a number of natural frequencies and mode shapes [8].
Although at a low level of excitation this experimental procedure is
very useful to validate the numerical results used to evaluate the
seismic behavior of dams [7].
Last two decade, some researchers have investigated
to dynamic behavior of large dams using both ambient and forced
vibration testing methods. In these studies it is highlighted that
although the physical conditions are hard as difficulties to excite of
large dams, and test become too expensive; results obtained AVT and FVT
are very attractive and useful [9-13]. Such kind of conditions made to researchers to construct scaled prototype dam models to study experimentally [14-18].
However, when constructing scaled dam models it is very important to
take great care in due to scaled models represent the real dam.
In this study, it is investigated that reservoir
level effects on the dynamic characteristics of a prototype arch dam
model using AVT and FVT. For this purpose, a prototype concrete arch
dam- reservoir-foundation model is constructed in the laboratory
conditions. Ambient and forced vibration tests are conducted to the arch
dam to identify dynamic characteristics for different reservoir levels,
and the variation of natural frequencies is determined using both
methods. The results showed that natural frequencies obtained for
different reservoir level from both methods are near to each other. It
is highlighted in the study that both of methods are very useful to
determine the dynamic behavior of arch dams.
Main Principles of Ambient and Forced Vibration Testings
Ambient vibration testing
Ambient excitation does not lend itself to Frequency
Response Function (FRFs) or Impulse Response Function (IRFs)
calculations because the input force is not measured in an ambient
vibration test. Therefore, a modal identification procedure will need to
base itself on output-only data [19].
There are several modal parameter identification techniques available
such as Peak Picking (PP), Stochastic Subspace Identification (SSI), and
Frequency Domain Decomposition techniques (FDD). These techniques are
developed by improvements in computing capacity and signal processing
procedures. In this study Enhanced Frequency Domain Decomposition
technique (EFDD) is used to extract dynamic characteristics of the arch
dam in OMA.
EFDD technique is an extension to FDD technique. FDD
is a basic technique that is extremely easy to use. In the technique,
modes are simply picked locating the peaks in Singular Value
Decomposition plots (SVD) calculated from the spectral density spectra
of the responses. As FDD technique is based on using a single frequency
line from the Fast Fourier Transform analysis (FFT), the accuracy of the
estimated natural frequency depends on the FFT resolution and no modal
damping is calculated. Compared to FDD, EFDD gives an improved estimate
of both the natural frequencies and the mode shapes and also includes
damping [20].
In FDD technique, the relationship between the unknown input x (t) and the measured responses y (t) can be expressed as [21]:

Where Gxx(jw)is the Power Spectral Density (PSD) matrix of the input, r is the number of inputs,Gyy(jw) is the mxm PSD matrix of the responses, m is the number of responses, H(jw) is the Frequency Response Function (FRF) matrix, and and *superscript T denote complex conjugate and transpose, respectively. Solution of the Equation (1) is given detail in the literature [22].
Forced vibration testing
The Frequency Response Function (FRF) is a
fundamental measurement that isolates the inherent dynamic properties of
a structure. Natural frequencies, mode shapes and damping ratios are
obtained from a set of FRF measurements. The FRF describes the
input-output relationship between two points on a structure as a
function of frequency. Since both force and motion are vector
quantities, they have directions associated with them. Therefore, an FRF
is actually defined between a single input DOF (point &direction),
and a single output DOF [23,24].
With Forced Vibration Testing the structure is artificially excited with a forcing function in a point i and its response yk (t) to this excitation is measured together with the forcing signal xk (t) (Figure 1). Transformation of these time signals into the frequency domain and calculation of all Frequency Response Functions (FRF) Hik
between the response and the forcing function time signals yields the
Frequency Response Matrix, also referred to as Transfer Matrix, H(iw) (Figure 2) [25].



In this study, FRF measurements of the arch dam are
obtained from impact testing. Because impact testing is a one of the
fast, convenient, and low cost way of finding the modes of structures.
Also, in small and medium size structures, the excitation can be induced
by an impulse hammer. But the selection of the hammer type can have a
significant effect on the measurement acquired.
The input excitation frequency range is controlled mainly by the
hardness of the type selected [26]. The schematic view of the impact testing is shown in Figure 3.
Experimental Example
Description of type-1 arch dam
In this study, Type-1 arch dam suggested "Arch Dams" Symposium in England in 1968 [27],
is selected for the experimental example. Type-1 arch dam has the
simplest geometry presented of the symposium. The geometrical properties
of Type-1 arch dam are shown Figure 4. As it is seen from Figure 4,
Type-1 arch dam has a single curvature, constant radius and constant
central angle. In addition, it has 6 unit height and 0.6 unit constant
widths. To construct a prototype model, 1 unit is selected as 10cm.
Therefore, dam height and crest width are designed as 60cm and 6cm,
respectively. 3D finite element model of Type-1 arch dam is constituted
by ANSYS [28] software (Figure 5).


Type-1 arch dam is developed including reservoir and
foundation. The reservoir is extended as 3H (H: dam height); the
foundation is extended as about H in the downstream and downward
directions, and is extended as reservoir length in upstream direction.
Such a modeling is appropriate to represent the dynamic response of
concrete dams [2]. Definitive dimensions of Type-1 arch dam-reservoir-foundation system are shown in Figure 6. Type-1 arch dam-reservoir-foundation system is constructed considering dimensions given in Figure 6. Some photographs related to dam are shown in Figure 7.


Ambient and forced vibration tests
Ambient and forced vibration tests are conducted to
Type- 1arch dam model to determine its natural frequencies, mode shapes
and damping ratios. Measurements are implemented for empty reservoir,
10cm, 20cm, 30cm, 40cm, 50cm reservoir levels and full reservoir.
The selection of measurement equipment, and
measurement setup such as measurement time and frequency span are so
important in the vibration tests. Because, measurement equipment and
setup are variable considering structure type. In the both vibration
tests, B&K 3560 data acquisition system with 17 channels and B&K
4507-B005 type uni-axial accelerometers are used. These accelerometers
have 1000mV/g sensitivity and 0.1-6000Hz frequency span. During the
tests, frequency span is selected 0-1600Hz according to finite element
results. Also B&K 8206-002 type impact hammer with 2.27mV/N
sensitivity and 4500N maximum force is used during the FVT.
During the AVT, measurements are performed along two
minutes, and excitations are provided from small impact effects. Signals
obtained from the tests are recorded and processed by the commercially
softwares PULSE [29] and OMA [30].
Dynamic characteristics of Type-1 arch dam are determined by EFDD
technique existed in OMA software. During the FVT, linear averaging
method is selected during the tests and number of the samples is
selected 5.FRFs of the measurements are obtained from PULSE software. In
the forced vibration tests, only the natural frequencies are determined
due to optional tools are not found in the test equipment to determine
mode shapes and damping ratios.
Ambient vibration tests and dynamic characteristics
of type-1 arch dam: Ambient vibration tests are conducted to dam for
empty reservoir, 10cm, 20cm, 30cm, 40cm, 50cmreservoir levels and full
reservoir. During the tests, eleven accelerometers are located to normal
direction of the water in the local axial along to crest of the dam (Figure 8). Some photographs from the tests related to each reservoir level are shown in Figure 9.


Singular values of spectral density matrices (SVSDM) of data set are shown in Figures 10-16 for each reservoir level, respectively. Mode shapes obtained from the tests for each reservoir level are shown in Figures 17-23.
Due to locations of the accelerometers is along to normal direction of
the water, only symmetrical and anti-symmetrical modes are obtained. The
natural frequencies and damping ratios obtained from the tests are
listed in Table 1.
Natural frequencies are not overly changed related to each mode shape
among 0-30cm reservoir levels, however the shift is overly increased
after 30cm. Also natural frequencies are reduced for the high reservoir
levels.
Forced vibration tests and natural frequencies of type- 1 arch dam:
Forced vibration tests are conducted to dam for the same reservoir
levels measured in AVT. During the tests, five accelerometers are
located to normal direction of the water in the local axial along to
crest of the dam (Figure 24). Some photographs related to each reservoir levels are shown in Figure 25. Frequency responses of the inputs are shown in Figures 26- 32. The natural frequencies of Type-1 arch dam are listed in Table 2.
















Variation of natural frequencies of type-1 arch dam: Variation of the first four natural frequencies obtained from AVT and FVT are plotted in Figure 33a-33d, respectively. As it is seen Figure 33,
the natural frequencies of Type-1 arch dam are not overly changed among
0-30cm reservoir levels. For the higher levels from half of dam height,
the natural frequencies are overly reduced. The variation ratios of the
natural frequencies for the empty and full reservoirs are given in Table 3.











Conclusion
In this study, the reservoir level effects on the
dynamic characteristics of arch dams are investigated using Ambient and
Forced Vibration Testings. For this purpose, a prototype model of Type-1
arch dam considering reservoir and foundation is constructed in the
laboratory conditions. To identify dynamic characteristics of the arch
dam, ambient and forced vibration tests are conducted for different
reservoir levels; and the variation of natural frequencies is determined
using both ambient and forced vibration tests. The following
observations can be made from the study: